Fire alarm and escape route drawings with a pen and a scale ruler

InsightsFire systems

What does a consultant review in alarm and detection systems?

Fire alarm and detection systems are a facility’s first line of defence: they pick up a fire early and warn everyone to leave. But detectors on the ceiling do not, on their own, mean the system works as it should. This article explains what a consultant reviews in these systems, from the drawings through testing, handover and maintenance.

The details of a review vary with each facility’s use, size and occupants. What follows is general professional practice; the exact requirements come from the applicable code and standard, and a licensed engineer confirms them for each project.

Why do alarm systems need a consultant’s review?

An alarm system usually passes through many hands: a designer, a supplier, an installation contractor and then an operations team. Every hand-over between them is a chance for a small gap that may only surface at inspection, or worse, on the day of an incident.

The consultant’s role is to hold those stages to one reference. The design is reviewed against the Saudi Building Code – Fire Code (SBC 801) and the applicable standards; then the consultant checks that what was installed matches what was approved on paper, and that the system actually works when tested.

What does the engineer look for in alarm drawings?

Alarm drawing review comes before any installation, because a mistake on paper is far easier and cheaper to fix than one in the ceiling. The engineer reads these drawings alongside the architectural drawings and those of the other systems, not in isolation.

  • Zoning: is the facility divided into clear alarm zones that help locate a fire quickly?
  • Coverage: do the detectors reach concealed spaces, plant rooms and corridors, not just the main halls?
  • Manual call points: are they placed where they are easy to reach along the exit routes?
  • Notification devices: do audible and visual alarms reach everyone, including people with hearing impairments?
  • Cable routes: are the routes, type and protection of the wiring suited to its role in the system?

The engineer also checks that the drawing reflects how the space is really used. A room that changes activity, or a new false ceiling, can change which detector suits it and where it goes.

How are smoke and heat detectors chosen and placed?

No single detector suits every space. The choice depends on the kind of fire expected there, and on conditions that could trigger false alarms, such as steam, dust or cooking fumes.

Common detector types and what the engineer weighs when choosing them
TypeOften preferred inWhat the engineer checks
Smoke detectorOffices, corridors and rooms where smoke is expected before flameDistance from air outlets and steam sources that cause false alarms
Heat detectorKitchens, car parks and spaces with routine dust or fumesThat its type suits the normal temperatures of the space
Multi-sensor detectorSpaces where conditions overlap and the choice is harderIts settings and compatibility with the control panel
Large-space detectionHigh halls, warehouses and atriumsThat the solution suits the ceiling height and air movement

Detector spacing, mounting heights and the number needed in each space are requirements set by the applicable code and standard, according to the ceiling’s shape and height and how the space is used. That is why each space is assessed on its own rather than one rule being copied across the building.

What is checked in the fire alarm control panel?

The fire alarm control panel is the system’s brain: it receives signals from detectors and call points, identifies where the event is, and triggers the alarms and linked actions. So the consultant reviews where it sits, how it is programmed and how it connects to the other systems.

  • Location: easy to reach and monitor, and protected from tampering and damage.
  • Programming: zone and device labels on the panel match what is on site, so an alarm’s location is clear at once.
  • Power supply: a main and a standby supply, sized to what the applicable standard requires for the facility.
  • Links to other systems: such as fire doors, lifts, smoke control, air conditioning and suppression systems.

The engineer also looks at the operating logic itself: what happens when one detector activates, and what happens when the alarm is confirmed. Wrong programming can stop a system that should run, or start one at the wrong time.

How does a consultant supervise fire system installation on site?

A good design is not enough if it is built differently from what was approved. So the engineer visits the site during the works, checks that the devices supplied match the approved specifications, and that installation follows the drawings.

A mall concourse fitted with fire detectors and sprinklers in the ceiling
On site, the engineer checks installed devices against the approved drawings.

Typical findings during supervision include a detector fitted next to an air-conditioning outlet, a false ceiling closed before the wiring above it was checked, or a device moved without the drawing being updated. See our engineering supervision of fire system installation.

What happens during alarm testing and commissioning?

Testing and commissioning is when the alarm system proves it works as one system, not a set of separate devices. It usually follows ordered steps attended by the consultant, the contractor and the owner’s representative:

  1. Visual inspection: the installed devices and their locations are checked against the approved drawings.
  2. Device testing: detectors and call points are activated and the right signal confirmed at the panel.
  3. Notification testing: audible and visual alarms are confirmed throughout the facility.
  4. Interface testing: linked systems are confirmed to respond to the alarm as designed.
  5. Records and handover: as-built drawings and test results are handed over, and the operations team is trained.

A system that has not been fully tested has not been handed over, however complete it looks in the ceiling.

Why does the review continue after handover? Periodic maintenance

Facilities change once they are in use: spaces are partitioned, rooms change activity, and dust builds up on detectors. Any of these can weaken fire alarm and detection systems without anyone noticing.

That is why the systems need periodic maintenance with proper records, its scope and frequency set by the applicable standard and the manufacturer’s instructions. Any change to the facility is reviewed before it is made, so the system does not drift from its approved design.

If you are planning a new facility or altering an existing one, the first step is fire and life safety design and review. To see what comes up most often in licence applications, read about common Civil Defense comments and how to avoid them.

Questions about fire alarm and detection systems

Usually not. A catalogue describes the device; whether it suits the facility, where it goes and how it links to other systems needs an approved design and review by a qualified engineer.

Often it is a detector that does not suit the space, a position near steam or a draught, or irregular maintenance. Fixing the cause is better than disabling the detector.

It helps, especially if the facility’s use or layout has changed since it was last approved. A review finds what no longer matches before it shows up at inspection.

The design engineer sets them according to the applicable code and standard and the nature of each space; they are then reviewed and approved as part of the drawings.